What's the maximum damping time I can set up for the Rosemount 8712?

Expert’s answer: What’s the Rosemount 8712 damping time?

You’re right, there’s a maximum Rosemount 8712 damping time. The device has its damping range limited to between 0.0 and 256 seconds. However, you need a good setup to avoid problems in the process control. Some technicians change the configuration, which winds up creating a bad value output.

Unfortunately, this change won’t solve a measurement problem. If your device setup hides the variation, then you ruin your measurement accuracy.

You should only use the damping configuration to stabilize small shifts in the process measurement. If you have a larger variation, then you should try to figure out the problem rather than raise your damping to obscure it.

Magmeter on the market:

Other resources that might interest you

Rosemount 8712 testing
Is there a tool that can simulate a flow meter?

Compressed air flow measurement on Rosemount 8800D
What to do when you experience a problem with compressed air flow measurement with the Rosemount 8800D vortex flow meter?

Rosemount 8712 and another flow sensor
Can you install a Rosemount 8712 with another brand sensor?

THUM with Rosemount 8712
How do you install a THUM with a wirelessHART network?

 

Related tags: commissioning Configuration damping Electromagnetic flow meter Magmeter setup
Comments
Rosemount 8712 damping time
#WishIknew: Types of mechanical flow meters
Buyer guide: ALTImass TypeU and Badger Meter RCT1000
If my digital manometer battery is dying, will I get bad measurements?
How to read the process variable from a multivariable flow meter
See related devices