Effect of electromagnetic pipeline mapper on magmeter
I'm looking for references and comments about the effects that an electromagnetic pipeline mapper can produce on a magnetic flow meter. I'd like to know any obstacle or special consideration when using both devices at the same time on a pipeline of more than ten kilometers. ...
Magmeter
I had a conversation with a Siemens rep today about the magmeters they want us to use on their equipment. He stated flat out that they don't care at all about flow runs or pipe and fittings before or after their flow meter. The two-inch model I saw had flanges about ten inches long on either side. W ...
What instruments to use for no-flow detection?
I need to detect a dead-end or no-flow condition. The fluid is liquid fertilizer and quite corrosive, and as heat builds up in the pumped fluid, it could explode. The pipe is six-inch stainless steel, and the flow rate 1000 liters per minute. What instruments could I use? ...
What’s the best way to do a meter accuracy test?
I have a magmeter measuring flow out of a tank. What's the best way to perform a draw down test to check its accuracy? ...
Problems when installing magnetic flow meter?
We need to cut a concrete sewer pipe and install a magnetic flow meter suitable for partially filled pipes. Can you foresee any problems with this installation? Will I need earthing rings? ...
Flow meter for process water
Hello. I need a flow meter, but I don't know exactly which type. The product will be process water with a maximum flow range of 100 m³/h and ambient temperature. It won't need much accuracy because it's just a monitoring application. Can you help? ...